American Power Conversion InfraStruXureTM System Power Supply User Manual


 
10 InfraStruXure System—Installation and Start-Up
Heat Output
Consider the heat dissipation ratings of equipment to determine cooling requirements. Additional
cooling equipment may be required. The following table shows the heat output of the InfraStruXure
PDU and the Symmetra PX UPS.
InfraStruXure PDU
208V 6,165BTU/hr. (1.81kW)
480V 5,079BTU/hr. (1.49kW)
600V 5,527BTU/hr. (1.62kW)
Symmetra PX UPS 23,757BTU/hr. (6.96kW)
Note
The heat output is higher while batteries are charging. Under normal operating
conditions, battery recharging periods are infrequent.