American Power Conversion InfraStruXureTM System Power Supply User Manual


 
Start-Up Procedure: InfraStruXure System
62 InfraStruXure System—Installation and Start-Up
Return from maintenance bypass operation
2. Close (turn ON) the Q2 circuit breaker on the InfraStruXure PDU.
1. Command the UPS into static bypass operation through the UPS display interface:
a. Press the
ESC key to open the top-level
menu.
Top-Level Menu
b. Select Control on the top-level menu, and
press the
ENTER key.
c. Select UPS Into Bypass on the Control
menu, and press the
ENTER key.
Control Menu
d. On the next screen: select Yes, UPS into
Bypass, and press the
ENTER key.
Confirmation Screen
Note
The H2 LED above the Q2 circuit breaker illuminates, indicating that it is safe to
operate the Q2 circuit breaker.
Note
The H3 LED above the Q3 circuit breaker illuminates, indicating that it is safe
to operate the Q3 circuit breaker