Table 5.6-3. Alarm Output Connections
5.7 Connecting The Loads
5.7.1 DC Circuit Breakers and Fuses
Both plug-in circuit breakers and GMT fuses can be installed in the MX28B power plant for dc
distribution circuit protection. Available plug-in circuit breakers are shown in Table 5.7-1.
Plug-in circuit breakers rated at 60A or more require two mounting positions and require a
breaker adapter kit, which is included (see kit selection information below the table). The
breaker adapter kit includes all necessary mounting hardware.
BREAKER
RATING
PART NUMBER BREAKER
RATING
PART NUMBER
1 A FFA-0014 40 A FFA-0020
3 A FFA-0015 50 A FFA-0025
5 A FFA-0016 60 A FFA-0021-X *
10 A FFA-0017 70 A FFA-0022-X *
15 A FFA-0028 80 A FFA-0023-X *
20 A FFA-0018 100 A FFA-0024-X *
30 A FFA-0019
* -1: adapter has #10 studs on 5/8” centers for two-hole cable lug
-2: adapter has #10 studs on ¾” centers for two-hole cable lug
-3: adapter has ¼” studs on 1” centers for two-hole cable lug
Table 5.7-1. Plug-in Circuit Breakers