American Power Conversion PD150L6F Power Supply User Manual


 
Overview: InfraStruXure PDU
12 150kW InfraStruXure PDU—Operation and Configuration
User connection plate
For a description and location of the user connection plate, see () on page 6. For clarity, the user
connection plate in the illustration below is shown in greater detail.
Connect the InfraStruXure PDU to the network or the InfraStruXure Manager through the
ethernet port.
The user connection plate has four input contact connections for monitoring Normally
Open (NO) or Normally Closed (NC) dry contacts. See page 20 and page 58 for more
information.
The user connection plate has four relay output connections for connection of Normally
Open (NO) or Normally Closed (NC) dry contacts. See page 20 and page 58 for more
information.
Connect an Emergency Power Off (EPO) switch at one of three choices of EPO
connections (24VDC, 24VAC, or contact closure). See page 60 for more information.