American Power Conversion PD150L6F Power Supply User Manual


 
150kW InfraStruXure PDU—Operation and Configuration 65
Specifications
150 kW InfraStruXure PDU
Electrical PD150G6F PD150L6F
Input
Nominal voltage 480V, 3-phase 600V, 3-phase
Voltage AC 3-phase, 3-wire 3-phase, 3-wire
Frequency 60Hz , ±3Hz 60Hz, ±3Hz
Max. current per phase 200A 150A
Load capacity 150,000VA 150,000VA
Max. crest factor 3 3
Output
Nominal voltage 120, 208V 1-phase and 208V 3-phase
Full load rating 150kVA
Nominal current 416A
Distribution breaker size 225A (maximum size)
Main panel breaker 400A MCCB
Subfeed breaker 150A/225A
Relay Outputs
Nominal switching capacity 1A at 30VDC
Maximum switching power 30W
Maximum switching voltage 60VDC
Maximum switching currant 2ADC
Maximum carrying current 2ADC
Surge ratings 2kV per Bellcore TA-NWT-001089
1.5kV per FCC part 68
Physical PD150G6F PD150L6F
Dimensions (H × W × D)
PDU 81 × 29 × 36in (2060 × 740 × 910mm)
Shipping 86 × 36 × 48in (2180 × 910 × 1220mm)
Weight
PDU only 1500lb (680kg) 1400lb (635kg)
PDU with 28 cables 1900lb (862kg) 1800lb (816kg)
Shipping 1950lb (885kg) 1850lb (839kg)