American Power Conversion PD150L6F Power Supply User Manual


 
16 150kW InfraStruXure PDU—Operation and Configuration
Load-Meter Screen
From the Load-Meter screen, you can select the following items:
Total Load by Phase The load supported by each phase in kilovolt-amperes (kVA), in
RMS current (Irms), and as a percentage of the maximum allowable
load (%LD).
Total Load Summary For the total load supported:
kW: The power provided, in kilowatts.
kVA: The actual power drawn by the load, in kilovolt-amperes.
Freq: The frequency.
PF: The power factor, which affects the power available to the
load.
%LD: The load as a percentage of the maximum allowable
load.
Power Factor For each phase:
kVA: The actual power drawn by the load, in kilovolt-amperes.
kW: The power, in kilowatts, provided by the phase.
PF: The power factor (kW/kVA) that affects the power
available to the load.