APC 20 - 200 KVA Power Supply User Manual


 
E-51028230XT/BG - 23
THE NUMBER OF UPS READY IS
INSUFFICIENT,
LOAD TRANSFER IN STAND BY
This message may be displayed in non-
redundant, parallel UPS systems,
when the number of ready inverters in
not sufficient to supply the load.
INVERTER NOT CONNECTED
This message may be displayed in
parallel UPS systems, when the
inverter is not connected to the load.
PARALLEL UPS,
FORCED TRANSFER INHIBITED
This message is displayed when forced
connection is requested on a parallel
UPS system for a power extension.
INTERNAL UPS FAULT,
SELF-TEST FAULT
Communication between the system
and the display is faulty. The buzzer
sounds slowly and discontinuously.
FORCED TRANSFER TO M2
REQUESTED,
POWER TO LOAD MAY BE
INTERRUPTED
CONFIRM YOUR REQUEST WITH
KEY
This message is displayed following
pressing of the "forced-transfer" key
2
0, when the load is supplied via the
inverter.
UPS SUPPLIED BY A GENERATOR
SET
This message informs the user that the
UPS has received the order to limit the
current drawn by the rectifier/charger.
It is displayed when the corresponding
signal is transmitted by the remote
indications board which must be
configured for this function.
THE BATTERY C.B. QF1 IS OPEN,
CHECK THE INSTALLATION
Battery circuit breaker QF1 is open.
The load is no longer protected
because battery power is no longer
available in the event of a normal AC
source outage. The buzzer sounds
continuously.
LOW BATTERY SHUTDOWN
The inverter has shut down at the end
of battery power. The buzzer sounds
continuously.
INTERNAL UPS FAULT,
INVERTER FAULT,
CALL MAINTENANCE
A fault has occurred in the inverter.
Servicing by the after-sales support
department is required. The buzzer
sounds continuously.
INTERNAL UPS FAULT,
CHARGER FAULT,
CALL MAINTENANCE
A fault has occurred in the rectifier/
charger. Servicing by the after-sales
support department is required.
The buzzer sounds slowly and
discontinuously.
FORCED TRANSFER TO INVERTER
REQUESTED, POWER TO LOAD
MAY BE INTERRUPTED,
CONFIRM YOUR REQUEST WITH
KEY
The requested transfer to the inverter
may provoke an interruption in the
supply of power to the load if Mains 2
characteristics are not within the
specified tolerances.
BYPASS SWITCH Q3BP
IS CLOSED
Maintenance bypass switch Q3BP is
closed. The system is in maintenance
configuration and the load is supplied
by the bypass AC source.
STATIC SWITCH (M2) OFF
DUE TO AN OVERLOAD
The load is no longer supplied by the
bypass AC source (M2), due to an
extended overload. The buzzer sounds
continuously.
BATTERY CHARGING
I BAT. = XXX A U BAT. = XXX V
The battery is currently being
recharged.
BATTERY AT END OF SERVICE
LIFE
CALL MAINTENANCE
The battery is nearing the end of its
estimated service life. This information
is based on average service-life
calculations since its initial installation.
The buzzer sounds slowly and
discontinuously.
EMERGENCY OFF OR FULL
SHUTDOWN
This message is displayed when either
the external emergency-off pushbutton
or the full-shutdown button
7 on the
control panel are pressed. The result is:
shutdown of the inverter;
shutdown of the rectifier/charger;
opening of the battery circuit breaker;
activation of a relay contact on the
remote-indications relay board.
To fully de-energise the installation,
these functions must also open the
external, upstream circuit breakers on
the normal and bypass AC supply lines.
The buzzer sounds continuously.
Control-panel display (cont.)