APC 20 - 200 KVA Power Supply User Manual


 
40 - E-51028230XT/BG
Empty cubicles
Cubicles may be supplied empty, thus
enabling users to make up their own
auxiliary cubicles (battery cubicles or
other) or panels and meet the particular
demands of each installation. In this
way, the entire electrical installation will
have a uniform appearance.
The following cubicles are available:
battery cubicles, 815 and 1015 mm
wide, 1.4 and 1.9 meters high;
auxiliary cubicles, 815 mm wide, 1.4
and 1.9 meters high.
Electrical supervision
"Teleservice"
"Teleservice" is a contract offering
continuous remote supervision and
maintenance of UPS systems via a
modem. Real-time communication is
established with our "Teleservice"
centre for communication of all alarms
and events occurring in the installation.
GTC board
This electronic board provides user
access to the J-Bus communications
protocol. Using the data and address
tables provided, the user can customise
his installation.
GTC + software
The user has access to the J-Bus
protocol and, in addition, the associated
software acquires system parameters
(measurements, status conditions) and
transforms them into diagrams, alarm
messages and tables. With the click of
a mouse, the user can locally or
remotely supervise the UPS system
(comprising one or many UPS units).
Management of computer
networks
Integrated SNMP agent
This electronic board, installed in the
UPS system, enables direct connection
to all Ethernet networks using TCP/IP.
The UPSs may then be supervised via
the computer network. Furthermore,
they can be used to close system files
without having to add an external
SNMP agent.
This board is fully compatible with
"Solution Pac
TM
" software.
0080C8ABAA01
The RJ45 connector of the
communications option delivers
information using the SNMP protocol.
The sticker located on the board
indicates the UPS MAC address.
your MAC address is written in the
following way : 0080C8 ZZ XX YY ;
your default IP address is 168.8.xx.yy
(xx and yy are
decimal values of XX and YY).
For example, MAC address 00 80 C8
AB AA 01 is related to IP address
168.8.170.1.
Please refer to the "userman.doc"
user manual contained in the
directory "emb/galaxy/snmp/
release3.xx" of the Solution-Pac CD-
ROM in order to discover the
management capabilities of your SNMP
MGE™ Galaxy™ PW UPS.
Please contact your sales
representative for more detailed
information.
Two-channel network board
This electronic board comprises two
ports, each of which may be user set,
either for the U-Talk protocol or as a
relay contact.
U-Talk is the protocol required to
establish contact with the
communications software.
Relay contacts may be used for specific
network applications (IBM AS400,
Novell, etc.).
Options (cont.)