APC 20 - 200 KVA Power Supply User Manual


 
E-51028230XT/BG - 35
Redundant, parallel UPS
See figures 27 and 28 in the Appendix.
During maintenance, a UPS unit must
be isolated from the normal AC source,
its battery and the output circuits of the
other UPS units.
isolate one UPS (see figure 27)
Proceed in the following order (see
figure 25 without Q3BP):
shut down the inverter (press the
"inverter OFF" button 9 for three
seconds),
open isolating switches Q5N, Q4S,
QF1 and Q1.
The UPS unit is powered down once
the capacitors have discharged (a few
minutes);
start-up
Following servicing, proceed in the
following order (see figure 26 without
Q3BP):
close switch Q1, then after
approximately ten seconds, switches
QF1, Q5N and Q4S,
start the inverter (press the "inverter
ON" button 8 ).
Note: if the load is still supplied
by an inverter, the Q3BP switch on
the unit undergoing maintenance
must not be closed.
To fully isolate the installation, proceed
as indicated below:
isolate all UPSs (see figure 28)
Proceed in the following order (see
figure 25):
shut down the inverters (press the
"inverter OFF" buttons
9 for three
seconds),
close the Q3BP switches used to
bypass the units (no units have
priority),
open isolating switches Q5N, Q4S,
QF1 and Q1.
The UPS units are powered down once
the capacitors have discharged (a few
minutes).
start-up
Following servicing, proceed in the
following order (see figure 26):
close switches Q1, then after
approximately ten seconds, switches
QF1, Q5N and Q4S,
open the Q3BP switches,
start the inverters (press the "inverter
ON" buttons
8 ).
Fig. 27 Fig. 28
1
D
2
B
A
Q3BP
Q1
Q5N
Q4S
QF1
C
1
D
2
B
A
Q3BP
Q1
Q5N
Q4S
QF1
C
1
D
2
B
A
Q3BP
Q1
Q5N
Q4
QF1
C
1
D
2
B
A
Q3BP
Q1
Q5N
Q4S
QF1
C
Maintenance (cont.)