4.4 UPS Characteristics
UPS characteristics are set at the factory for normal operation and usually
do not need to be changed. However if a change is needed, select items
from the
UPS Characteristics menu. New settings may conflict with the
operation of UPS monitoring software in use, so check the requirements
of the system before changing them. Default and optional values for these
settings vary from one UPS to another.
Note: Smart-
UPS products with serial numbers beginning with
the letter W do not support reporting and setting
UPS
characteristics with Call-UPS II. In this case, item 3, UPS
Characteristics will not appear on the Main menu.
To display or change the characteristics of the
UPS, type 3 and press
ENTER from the Main menu. The appearance of the UPS Characteristics
menu will vary according to the type of the connected
UPS. Refer to the
appropriate sections and accompanying tables that follow.
With Smart-UPS and Matrix-UPS
Call-UPS II connected to a Smart-UPS or Matrix-UPS displays the follow-
ing UPS Characteristics menu:
------------------- UPS CHARACTERISTICS -----------------
UPS ID: UPS_IDEN
1- Output: 240 V
2- Output Freq Range: AUTO
3- Output Voltage Reporting base: Auto
4- If UPS fails and freq or voltage is out of
range: Go to Bypass
---------------------------------------------------------
5- Low Battery Duration: 02 min.
6- Shutdown Delay: 020 sec.
7- Return Delay: 000 sec.
8- Return Battery Capacity: 00 %
9- Scheduled Self Test: every 14 Days
---------------------------------------------------------
10- Alarm if runtime is less than: 000 min.
11- Alarm if load is greater than: 00.0 kVA
12- Alarm if redundancy is less than: n+2 (0=never)
---------------------------------------------------------
13- Reset UPS to Default Settings
?- Help
<ENTER> Display Menu
<ESC> Return to Previous Menu
>