USER’S GUIDE
network management card
58
Battery Thresholds. From the Batteries sub-menu, type 2 to display and
configure Battery Thresholds:
Menu Item Description
1-Float Voltage (V) The DC Power Plant voltage, in volts
Minimum: – 58.00
Maximum: – 40.00
2- Max Recharge (A) The battery maximum recharge rate, in amps.
Minimum: 0
Maximum: The maximum possible output power of your
specific DC Power Plant model.
3- Discharge Threshold (A) If battery output current exceeds this threshold (in
amps), the battery discharge alarm occurs.
Minimum: 0
Maximum: 200.00
4- High Voltage Threshold (V) If system battery voltage exceeds this threshold (in
volts), the battery high voltage alarm occurs.
Minimum: – 60.00
Maximum: – 40.00
5- Low Voltage Threshold (V) If system battery voltage drops below this threshold (in
volts, the battery low voltage alarm occurs.
Minimum: – 60.00
Maximum: – 30.00
6- High Temperature
Threshold
If system battery temperature in Celsius exceeds this
threshold, the battery high temperature alarm occurs.
Minimum: – 100.00
Maximum:
200.00
7- Low Temperature
Threshold
If system battery temperature in Celsius drops below
this threshold, the battery low temperature alarm
occurs.
Minimum: – 100.00
Maximum: 200.00