Battery Alarms. From the Batteries sub-menu, type 3 to display and
configure Battery Alarms:
Menu Item Description
1- Discharge
Alarm
The alarm action that occurs if battery output current exceeds the
Discharge Threshold. See Battery Thresholds.
Allowed values: any standard alarm selection
a
.
2- High Voltage
Alarm
The alarm action that occurs if system battery voltage exceeds the
High Voltage Threshold. See Battery Thresholds.
Allowed values: any standard alarm selection
a
.
3- Low Voltage
Alarm
The alarm action that occurs if system battery voltage drops below
the Low Voltage Threshold. See Battery Thresholds.
Allowed values: any standard alarm selection
a
.
4- High
Temperature
Alarm
The alarm action that occurs if system battery temperature exceeds
the High Temperature Threshold. See Battery Thresholds.
Allowed values: any standard alarm selection
a
.
5- Low
Temperature
Alarm
The alarm action that occurs if system battery temperature drops
below the Low Temperature Threshold. See Battery Thresholds.
Allowed values: any standard alarm selection
a
.
6- Hardware
Current Alarm
The alarm action that occurs if the battery current is outside
reasonable limits or if a measurement fault occurs.
Allowed values: any standard alarm selection
a
.
7- Hardware
Temperature
Alarm
The alarm action that occurs if the battery temperature is outside
reasonable limits or if a measurement fault occurs.
Allowed values: any standard alarm selection
a
.
a
Standard alarm selections:
• Major activates the major relay.
• Minor activates the minor relay.
• Relay 1 through Relay 6 activates the relay specified.
• Ignore ignores the alarm.