APC SYBATT Power Supply User Manual


 
CHAPTER 3: MENU COMMANDS
14
Setup Menu (continued)
Menu Item Function Options
Alarms Sets the alarm thresholds. None
Redundancy An audible alarm sounds if the redundancy falls
below this level.
0 (default), 1, or 2
Load An audible alarm sounds when the load exceeds
this limit. (Upper value is limited by the maximum
power of the UPS.)
Never (default), 1, 2, 3, 4, 5,
6, 7, 8, 9, 10, or 12 kVA
Runtime An audible alarm sounds if the available runtime
falls below this level (Hours:min).
0:0 (default),5m, 10m, 15m,
30m, 45m,1h, 2h, 3h, 4h, 5h,
6h, 7h, or 8h
Bypass If the UPS fails and the input voltage or line
frequency is outside of normal range, this option
allows the user to choose Bypass mode, or drop the
load.
Go to Bypass or
Drop Load
Copy Select the configuration that you wish to move UPS
data into or out of, and then select the direction that
you wish to move the data.
Note: Copying data between different voltage
versions may not yield optimum results. The output
voltage selection should be reviewed by the user.
Copying between different product lines may leave
some parameters in the target UPS set to factory
defaults, especially when copying from a product
with lesser capability.
Options include:
Configuration Number, from
UPS to Display, and from
Display to UPS.
Copy command definition
found in Powerview manual,
990-0142, page 11.
Other Remaining user-defined settings.
Self Test The UPS can automatically test itself at this user-
specified interval.
At Power On, 7 days,
14 days (default) , or
Disabled
UPS ID Assigns an eight-character text string to a system.
Output Sets output voltage. Selection depends upon
system configuration.
US/JAPAN:
200 V, 208 V, 240 V
INTERNATIONAL:
220 V, 230 V, 240 V
Vout Reporting Reports the most significant output voltage. Auto