APC SYBATT Power Supply User Manual


 
CHAPTER 4: TROUBLESHOOTING
16
Condition PowerView Message Reason Corrective Action
AC adequate for UPS but
not for bypass.
The UPS will function on-line with
the input voltage. But, in the event
that bypass is required, the input
voltage is not adequate to power
the load equipment.
Option 1: Improve the
incoming voltage.
Option 2: Proceed with start-
up. Normal bypass is not
available.
Start-Up
(continued)
Low/No AC input, start-up
on battery.
Input voltage is not adequate to
start the UPS. If start-up
continues, the UPS will function
from battery.
Option 1: Abort start-up until
acceptable input voltage is
present.
Option 2: Proceed with start-
up. Battery will be discharged.
# of batteries increased. At least one battery module has
been added to the system.
# of batteries decreased. At least one battery has been
removed from the system.
# of Pwr Modules
increased.
At least one power module has
been added to the system.
Intelligence Module
inserted.
An intelligence module has been
installed in the lower IM slot.
Intelligence Module
removed.
An intelligence module has been
removed from the lower IM slot
Redundant Intelligence
Module inserted.
An intelligence module has been
installed in the upper IM slot.
Redundant Intelligence
Module removed.
An intelligence module has been
removed from the upper IM slot.
# of External Battery
Cabinets increased.
At least one external battery
cabinet has been connected to the
frame.
# of External Battery
Cabinets decreased.
At least one external battery
cabinet has been disconnected
from the UPS.
General
Status
Redundancy Restored. Power module redundancy loss
occurred and was restored. Either
additional modules have been
installed or the load has been
reduced.
No corrective action is
necessary.