APC SYBATT Power Supply User Manual


 
CHAPTER 2: BASIC COMMANDS
5
5. In approximately 90 seconds, the green Load On indicator will illuminate and this message will appear.
UPS LOAD IS ON
Press any key…
Turn Off UPS Output Power and Load Equipment
1. Press ‘Esc’ until the Main Menu appears.
>Control Logging
Status Display
Setup Diags
Accessories Help
2. Scroll down and select the ‘Turn UPS Output Off’ command.
Graceful Turn Off
Start Runtime Cal
>Turn UPS Output Off
3. Confirm choice by selecting ‘YES’.
Confirm:
Turn UPS Off
NO, ABORT
>YES, Turn UPS OFF
You will hear some clicking sounds and see the following message.
UPS HAS BEEN
COMMANDED TO TURN
LOAD POWER OFF
In approximately 90 seconds, you will see the following message and the green Load On status indicator will
be OFF.
The output is now off.
UPS LOAD IS OFF
Press any key…
4. To fully remove power from the UPS, turn OFF the system enable switch, and open the input circuit breaker.
Bypass Operation
The bypass operation can be performed manually, using the maintenance bypass switch, or automatically, using
the PowerView to issue commands.
In either bypass mode, the utility and circuit breakers must be turned on.
The UPS must remain functional to stay in command bypass mode. Put the UPS in maintenance
bypass before turning off the system enable switch, or removing both intelligence modules.