CHAPTER 2: BASIC COMMANDS
3
Basic Commands
Supply Power to the UPS
This procedure supplies power to the Symmetra LX and does not supply power to the equipment connected to
the UPS.
1. Turn ON the AC utility power to the UPS
2. Switch ON the circuit breakers for all connected equipment.
a. If connected equipment is hardwired, check that the output circuit breakers in the distribution panel are
turned ON.
b. If connected equipment is plugged into the UPS
! , check that each UPS PDU output circuit breaker "
is switched ON.
3. Switch ON the UPS input circuit breaker # .
4. Turn ON the UPS system enable switch $ .
To start the UPS when there is no AC utility power present, press and hold either of the cold start
buttons
% for four seconds.
5. After initialization, the monitoring screen appears, providing a view of operating parameters.
Chg100%
Load 000%
220 Vin 000 Vout 60Hz
Runtime: 00hr 30min