Compaq R6000 Series Power Supply User Manual


 
Configuration
4-21
Compaq Confidential – Need to Know Required
Writer:
Daniel E. Lyons
Project:
Compaq R6000 Series UPS Operation and Reference Guide
Comments:
Revised as per A. May
Part Number:
347223-022
File Name:
e-ch4.doc
Last Saved On:
3/24/99 1:44 PM
Set Voltage
The Compaq R6000 UPS must be placed in manual Bypass using the switch at
the rear of the unit, and placed into Standby mode (see Chapter 3,
“Operation”) to set the voltage.
The voltage that is set will appear with an “*”. Using the Center button, scroll
through the voltages and choose using the Enter button. The choices are:
200 V
208 V
220 V
230 V
240 V
208/230 V Auto Sensing
230 V Extended
Set Voltage
208V
Set Site Fault
The two values are “Disable” or “Enable.” Use the Center button to scroll and
the Enter button to select. An asterisk, “*” marks the selected value.
Set Site Fault
Enable
Set Sleep Mode
When Sleep Mode is enabled, if the UPS is supplying battery power and the
load on the UPS is less than 8%, the UPS switches to Sleep mode (the UPS
shuts itself off). Use the Center and Enter buttons to “Enable” or “Disable”
this feature. An “*” will mark the selected value.
Set Sleep Mode
Enable