Table 6-6
Responding to Audible Alarms
continued
Audible Alarm Group Audible Alarm Sound Cause(s) Action
Caution
(continued)
Beeps every five
seconds.
The charger fails. Call an authorized service
provider.
A fan fails. Call an authorized service
provider.
UPS unable to charge
batteries.
See Chapter 2, “Installation”
on procedures to check battery
connections and make sure
battery breaker is in the ON
position. Run UPS for 24 hours.
If condition still does not clear,
contact an authorized service
provider.