Table 6-5
Warning
Audible Alarm
Audible Alarm Group Audible Alarm Sound Cause(s) Action
Warning
Beeps every half
second
Running out of battery
power while on battery.
Check LCD display (Battery
Data) and run again.
The self-test fails. Check LCD display (Battery
Data) and run again.
The battery test fails. Check LCD display (Meters,
Battery Voltage); if voltage is
low, refer to Chapter 2,
“Installation” to check
battery connections, or if a
battery breaker is in the ON
position. Run battery test
again, or replace batteries.
Heat sink over
temperature while UPS
not on battery.
Check to make sure the
airflow around and to the
UPS is not restricted. Check
the room’s ambient
temperature. If warning
alarm still sounds, contact
an authorized service
provider.
Overvoltage condition Cycle the input power (turn
the mains circuit breaker
OFF, then ON. If condition
remains, contact an
authorized service provider.