Standard Operating Temperature
Ambient temperature is restricted to 30°C for the
R630 system with 10X 2.5 inches drives chassis,
with no PCIe SSD and a maximum of 135 W CPU.
Ambient temperature is restricted to 35°C for the
R630 system with 10X 2.5 inches drives chassis,
with no PCIe SSD and a maximum of 120 W CPU.
Ambient temperature is restricted to 35°C for the
R630 system with 24X 1.8 inches drives chassis,
SSD, and a maximum of 135 W CPU.
Expanded Operating Temperature
NOTE: When operating in the expanded temperature range, system performance may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be
reported on the LCD and in the System Event Log.
Continuous Operation 5°C to 40°C at 5% to 85% RH with 29°C dew point.
NOTE: Outside the standard operating
temperature (10°C to 35°C), the system can
operate continuously down to 5°C or as high
as 40°C.
For temperatures between 35°C and 40°C, de-
rate maximum allowable temperature by 1°C per
175 m above 950 m (1°F per 319 ft).
< 1% of annual operating hours –5°C to 45°C at 5% to 90% RH with 29°C (84.2°F)
maximum dew point.
NOTE: Outside the standard operating
temperature (10°C to 35°C), the system can
operate down to –5°C or up to 45°C for a
maximum of 1% of its annual operating hours.
For temperatures between 40 °C and 45 °C, de-
rate maximum allowable dry bulb temperature by
1°C per 125 m above 950 m (1°F per 228 ft).
Expanded Operating Temperature Restrictions
Do not perform a cold startup below 5°C.
The operating temperature specified is for a
maximum altitude of 3048 m (10,000 ft).
PCIe SSD and 1.8 inch SSDs are not supported.
GPU is not supported.
145 W and Workstation CPU (160 W)
processors are not supported.
Two power supply units are required and one
power supply unit failure is not supported.
Non Dell qualified peripheral cards and/or
peripheral cards greater than 25 W are not
supported.
157