11.4 Battery Run Times
Table 35 Estimated battery run time, minutes
UPS Rating/Model
Number of Cabinets
123 4
40kVA UPS
UPS12-100MR 5 18 32 47
UPS12-150MR 13 33 53 75
UPS12-210MR 21 51 81 123
60kVA UPS
UPS12-100MR - 9 18 27
UPS12-150MR 7 19 33 47
UPS12-210MR 11 31 51 73
80kVA UPS
UPS12-100MR - 5 11 18
UPS12-150MR - 13 22 33
UPS12-210MR 6 21 36 51
100kVA UPS
UPS12-100MR - - 8 12
UPS12-150MR - 9 17 25
UPS12-210MR - 15 27 38
120kVA UPS
UPS12-100MR - - 5 9
UPS12-150MR - 7 13 19
UPS12-210MR - 11 21 31