Emerson 480V Power Supply User Manual


 
Installation Drawings
39
Figure 24 Cable connections
965
(38")
600
(23.6")
2000
(78.7")
LEFT SIDE VIEW
(with side panel removed)
FRONT VIEW
(with door removed)
20 (.79")
35
(1.38")
158.1
(6.22")
35
(1.38")
36 (1.42")
Output
GND
DC
Bypass
Main
25.4
(1")
6
(.24")
CB1 CB2 CB3 CB5
NOTES
1. All dimensions are millimeters (in.).
2. Top and bottom cable entry available
through removable access plates.
Remove, punch to accommodate
conduit size and replace.
3. Control wiring and power wiring
must be run in separate conduit.
Output and input cables must be run
in separate conduit.
4. Aluminum and copper-clad
aluminum cables are not
recommended.
5. All wiring is to be in accordance with
national and local electrical codes.