Emerson 480V Power Supply User Manual


 
UPS Specifications
34
5.4 UPS Electrical Characteristics
Table 8 UPS terminal
Input (For Single-Input Unit)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP
Device
Rating
Bolt
Size
Maximum Recommended Lug
(Thomas & Betts part number)
Compression
2-Hole;
3/8" Bolt
Mechanical
2-Hole;
40 48 66.8 80.2 90 8M 54106 ADR21
60 72 100.2 120.3 125 8M 54108 ADR21
80 96 133.6 160.4 175 8M 54157 ADR21
100 120 167.1 200.5 225 8M 54167 ADR50
120 144 200.5 240.6 250 8M 54172-TB ADR50
Rectifier input (for dual input unit only)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP
Device
Rating
Bolt
Size
Maximum Recommended Lug
(Thomas & Betts part number)
Compression
2-Hole;
3/8" Bolt
Mechanical
2-Hole
40 48 67.5 83 90 8M 54106 ADR21
60 72 101.3 124.5 125 8M 54108 ADR21
80 96 135 166 175 8M 54157 ADR21
100 120 168.8 207.6 225 8M 54167 ADR50
120 144 202.5 249.1 250 8M 54172-TB ADR50
Bypass input (for dual input units)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Device
Rating
Bolt
Size
Maximum Recommended Lug
(Thomas & Betts part number)
Compression
2-Hole;
3/8" Bolt
Mechanical
2-Hole
40 48 66.8 70 8M 54106 ADR21
60 72 100.2 110 8M 54107 ADR21
80 96 133.6 150 8M 54152-TB ADR21
100 120 167.1 175 8M 54157 ADR21
120 144 200.5 225 8M 54167 ADR50
Output
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Device
Rating
Bolt
Size
Maximum Recommended Lug
(Thomas & Betts part number)
Compression
2-Hole;
3/8" Bolt
Mechanical
2-Hole
40 48 66.8 70 8M 54106 ADR21
60 72 100.2 110 8M 54107 ADR21
80 96 133.6 150 8M 54152-TB ADR21
100 120 167.1 175 8M 54157 ADR21
120 144 200.5 225 8M 54167 ADR50