Emerson 480V Power Supply User Manual


 
Installation Drawings
44
Figure 29 Outline drawing, Liebert NX480V, 80-120kVA Type E and E2 parallel cabinet
To p
Right Side
800
(31.5)
965
(38)
Front
2000
(78.7)
NOTE:
1. All dimensions are in millimeters (in).
2. Eight-inch minimum clearance above unit required for air
exhaust.
3. Keep cabinet within 15 deg. of vertical while handling.
4. Top and bottom cable entry available through removable
access plates. Remove access plate, punch to suit conduit size
and replace.
5. Color - black.
6. Unit bottom is structurally adequate for forklift handling.
7. M10 threaded mounting holes used for seismic anchoring or
floor stand.
NOTE: If floor stand is used, the weight of the unit must be
supported under all casters.
8. Each mounting location is supported by two 10 ga. (.135")
galvanized steel. The threaded insert is approximately 3/4"
deep. Mounting holes are underneath unit base; mounting
bolts must be threaded into unit.
9. Side panels must be removed from adjacent units that are
bolted together.
10. Leveling feet are not designed to carry the full weight of the
cabinet. Finger-tighten leveler against the floor, then tighten
with a wrench less than 2 turns for friction fit against floor.