Emerson 480V Power Supply User Manual


 
Options
81
10.0 OPTIONS
Several items of optional equipment are available for connection to the Liebert NX UPS.
10.1 Communication and Other User Terminals
The UPS can be integrated into advanced networking environments via UPS monitoring software
such as Windows-based UPS Monitor, MultiLink
, Nform
, SiteNet, Modbus / Jbus, SiteScan,
SiteScan 2, SNMP, etc. They allow UPS status monitoring and automatic and safe shutdown of the
server and PCs.
Figure 55 Monitoring board (U2) auxiliary terminal block detail
10.1.1 Analog Input Interface
At the X6 slot, there are two analog signal channels. Input range is from 0 to +5V, and the precision is
2 percent. “ENV-T” is used for environment temperature detecting.
X6 pin 1: Not used
X6 pin 2: +12V
X6 pin 3: ENV-T – environment temperature detection
X6 pin 4: GND
10.1.2 Power Output
The X5 slot can provide power for a modem or an external SNMP card. Available voltage is from 9V to
12V. The maximum current is 500mA.
10.1.3 Liebert IntelliSlot Communication
The Liebert NX has three Liebert IntelliSlot ports to allow field-installation of optional communica-
tion cards. Liebert IntelliSlot cards communicate via Liebert’s proprietary ESP2 protocol to cards that
translate the information into such protocols as SNMP, IGMnet, Modbus or Jbus. Other cards provide
dry contact signals for external signaling of operating status.
The Liebert IntelliSlot communication ports may be installed or removed while the Liebert NX is
operating.
NOTE: The black square ()
on each slot indicates Pin 1.
J3
J1
J13 J21 J25 J28 J4 J26 J30 J10
J22
J23
J12
J9
J15
J17
J24
X4
X4
J16
X1 X2 X3
Liebert IntelliSlot 2
Liebert IntelliSlot 1
Liebert IntelliSlot 3
J8
J2
LCD
BFP INV ACF EPO Dry in MBC BCB
X5
X6
X7
PWR
MODEM
SNMP CARD