Emerson 5081-T Switch User Manual


 
52
MODEL 5081-T SECTION 7.0
PROGRAMMING
7.2.3 Procedure
1. Press PROG on the remote controller. The OutPut submenu appears.
2. Press ENTER. The screen displays the 4 MA prompt. Use the arrow keys to change
the setting. Press ENTER to save.
3. The screen displays the 20 MA prompt. Use the arrow keys to change the setting.
Press ENTER to save.
4. The screen displays the HoLd prompt. Use the arrow keys to change the setting to
the output desired when the transmitter is in hold. The range is 3.80 to 22.00 mA.
Entering 00.00 causes the transmitter to hold the output at the value it was when
placed in hold. The hold setting overrides the fault setting. Press ENTER to save.
5. The screen displays the FAULt prompt. Use the arrow keys to change the setting to
the output desired when the transmitter detects a fault. The range is 3.80 to 22.00 mA.
Entering 00.00 causes the transmitter to hold the output at the value it was when the
fault occurred. Press ENTER to save.
6. The screen displays the dPn prompt. Use the arrow keys to change the setting. The
range is 0 to 255. Press ENTER to save.
7. The screen displays the tESt prompt. Use the arrow keys to enter the desired test cur-
rent. Press ENTER to start the test. Press EXIT to end the test.
8. Press RESET to return to the process display.