4.2. Client Side Connection Descriptions
Section Title
Connections
Column Title Function Legal Values
Port
Specify which port the device is connected
to the FieldServer
P1-P8, R1-R2
3
Baud* Specify baud rate
110 – 115200, standard baud
rates only.
Parity* Specify parity
Even, Odd, None, Mark,
Space
Data_Bits*
Specify data bits
7, 8
Stop_Bits*
Specify stop bits 1
Protocol
Specify protocol used sim4100
Handshaking*
Specify hardware handshaking RTS, RTS/CTS, None
Poll Delay*
Time between internal polls
0-32000 seconds, 1 second
Example
// Client Side Connections
Connections
Port, Protocol, Baud, Parity, Handshaking, Poll_Delay
P8, Sim4100, 9600, Even, None, 0.100s
4.3. Client Side Node Descriptors
Section Title
Nodes
Column Title
Function Legal Values
Node_Name
Provide name for node Up to 32 alphanumeric characters
Node_ID Ad
This parameter is IGNORED. Special
keywords to define the card-sub-point
are described in section 4.4
Protocol Specify protocol used Sim4100
Port
Specify which port the device is
connected to the FieldServer
P1-P8, R1-R2
3
PLC_Type*
Required for Simplex4100 Panels.
If not specified then a Simplex
4100/4020 panel is assumed.
4020/4100 - panels with firmware
version 9x or earlier.
4100U – panels with firmware
version 10x or later.
4100, 4020, 4100U
3
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.