FieldServer FS-8700-41 Computer Drive User Manual


 
FS-8700-41 Simplex 4100 Driver Manual Page 33 of 58
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
Appendix A.10. Advanced Map Descriptor Example 1 - Errors
If an error response is received from the panel then if a Map Descriptor similar to this one is defined, the driver will store the error
message (and some information about the Map Descriptor that caused the error) in the Data Array DA_ERRORS.
It is best to define the DA_ERRORS array as format BYTE and if you use RUINET to monitor this Data Array change the display
format to string so that you can read the error. Refer also to Appendix B.1.
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, sim4100_func, Length
Error_Mapdesc, DA_ERRORS, 0, passive, Node_A, Errors, 200
Appendix A.11. Advanced Map Descriptor Example 2. - Read Panel Time
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, sim4100_func, Scan_Interval, Length
Time_Mapdesc, DA_TIME, 0, RDBC, Node_A, Time,, 30s, 70
Index 0: Hour (24 hour clock)
Index 1: Minute
Index 2: Second
Index 3: Day of week
Index 4: Day of month
Index 5: Month
Index 6: Year (since 2000)
Must be passive.
Most recent error returned by the panel is
stored here. Subsequent errors overwrite
the data in this array.