FieldServer FS-8700-41 Computer Drive User Manual


 
FS-8700-41 Simplex 4100 Driver Manual Page 48 of 58
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
Error Message Troubleshooting Tip
Sim4100:#54. Err. SeqNumber check
disabled.
Sequence number checking was disabled. Check
your password. Contact FieldServer Technologies
for support.
Sim4100:#55. Error. Bad
Sim4100_Func=%d in MD=<%s>
Check the CSV file for the correct Simplex function
type.
Sim4100:#56 Not used.
Sim4100:#57* Err. Cant parse Login
message. Ignored.
The driver ignored Login messages. No corrective
action is required. This message is printed for your
information only.
Sim4100:#58 FYI. You could have used
an Array called <%s> to expose
diagnostic info.
This message is printed for your information only. It
can safely be ignored. For additional information
read section “Appendix A.7.2 Driver Exposed Stats”
Sim4100:#59 Err. Checkpoint. Report
this to Tech Support.
An internal driver diagnostic has been triggered.
You must report this error to FieldServer’s
Technical Support.
Sim4100:#60 Err. MapDesc=%s. No
Node.
Every Sim4100 Map Descriptor must be connected
to a node. Ensure that the parameter ‘Node_Name’
has been specified on the Map Descriptor.
To correct this problem, edit the CSV, make the
correction, download the corrected CSV file and
reset the FieldServer.
Sim4100:#61 Err. PLC_Type=4100u
rqd for 'values'/'earths'
If you have a Map Descritor which has the
sim4100_func parameter set to ‘earths’ or to
‘values’ then you must set the PLC_Type
parameter on the node to 4100U. (See section 0
Client Side Node Descriptors ). It is only
appropriate to do so if the firmware version of your
panel is 10.x or later. You can create a map
descriptor to read the version information if you are
not sure. You can also use the menu system on the
Panel to read the version number.
To correct this problem, edit the CSV, make the
correction, download the corrected CSV file and
reset the FieldServer.
Sim4100:#62 Err. Input Buffer Overflow.
This message is printed when the input buffer
overflows. This usually occurs when the panel
sends lots of messages and they are not being
processed by the driver fast enough. A panic is
printed immediate after this message.
The driver will clear the buffer and start capturing
new bytes as they arrive. Messages may have
been lost. We advise that you re-synch the panel.
This error has only been seen once. It occurred
when a panel was connected to the driver with the
wrong connection settings.