GE LP11U Power Supply User Manual


 
LX: OPM_LPU_11U_5K0_10K_1US_V030 31 GE DE LP 11U UPS: Installation / User Manual 3.0 (US)
Digital En
e
rg
y
LP Serie
s
g
Controls functioning of the automatic bypass switch. Range:
ENABLED/DISABLED. If the UPS is used as a frequency converter you may
change the setting to ‘DISABLED’. Bypass operation will then be inhibited and
all alarms related to ‘bypass out of limits’ are suppressed.
The system can prompt for service to a user defined schedule.
Range: 8/12/16/20/24/28 months or DISABLED. To reset the timer: first select
“DISABLED” and subsequently set a new alarm interval.
5.4 Test Screens
These screens show the test procedure, either started from the service menu (front panel keys) or via the UPS
monitoring software (RS232/SNMP). The upper line indicates the kind of test, the second line its status.
Upper lines: second line:
GENERAL SYSTEM
GENERAL SYSTEMGENERAL SYSTEM
GENERAL SYSTEM
TEST START
TEST STARTTEST START
TEST START the test will start soon
QUICK BATTERY
QUICK BATTERYQUICK BATTERY
QUICK BATTERY
TEST ACTIVATED
TEST ACTIVATEDTEST ACTIVATED
TEST ACTIVATED the test is running
CALIBRATE BAT
CALIBRATE BATCALIBRATE BAT
CALIBRATE BAT
TEST SUCCESFUL
TEST SUCCESFULTEST SUCCESFUL
TEST SUCCESFUL the test has been completed succesfully
BYPASS
BYPASSBYPASS
BYPASS
TEST FAILED
TEST FAILEDTEST FAILED
TEST FAILED the test has not been completed succesfully
5.4.1 Battery Test, general
Automatic test: Every 500 operating hours the UPS conducts automatic battery tests to ensure that the
batteries and the wiring are able to support power failures. The tests do not cause any interruption in the
functioning of the unit.
Manual test: A manual battery test can be activated
- either through an interface kit, via the RS232 or SNMP Interface Port (please refer to the manual of
your interface package), or
- via the front panel: see below
5.4.2 Quick Battery Test
From the standard menu first enter the service menu (press the 'down' and 'Enter/Reset' keys simultaneously,
then press the 'down' key until the following screen appears:
The ‘Enter/Reset’ key confirms the selection, and the screen shows:
The test status (indicated by the second line) can be:
TEST ACTIVATED
TEST ACTIVATEDTEST ACTIVATED
TEST ACTIVATED = testing
TEST SUCCESSFUL
TEST SUCCESSFULTEST SUCCESSFUL
TEST SUCCESSFUL = battery has been tested with positive result
TEST FAILED
TEST FAILEDTEST FAILED
TEST FAILED = the batteries should be replaced
NOT AVAILABLE
NOT AVAILABLENOT AVAILABLE
NOT AVAILABLE = battery capacity too low to start the test
If the batteries are dangerously close to being worn out, a low priority alarm 'replace battery' will be generated.
The batteries must be replaced as soon as possible (see section 8.3).
NOTE: If the manual test is started immediately after installation or after a power failure, the UPS may generate
a false 'replace battery' alarm as the batteries have been (partly) discharged during transport/storage or during
the power failure.
QUICK BATTERY
TEST PRESS ENTER
QUICK BATTERY
TEST START
AUTOMATIC BYPASS
ENABLED
SERVICE WARNING
DISABLED