GE LP11U Power Supply User Manual


 
Digital Energy
LP Serie
s
g
LP 5/6/8/10-11U installation drawings
Model Heat dissipation
Linear load 240 Volt
Dimensions Air flow
100%
load
Rel.
humidity
non-cond.
Altitude
(max 4000m)
Input wiring Output wiring
100% load 50% load h w d
Weight
Amb.
temp.
utility volt.
120V
utility volt.
208V
utility volt.
240V
output
volt. 120V
output
volt. 208V
output
volt. 240V
LP-U W Btu/hr W Btu/hr Inch Inch Inch Lbs m3/hr °F m
AWG/mm
2
AWG/mm
2
AWG/mm
2
AWG/mm
2
AWG/mm
2
AWG/mm
2
5-11 571 1950 389 1329 26.8 12.3 28.7 295 660 14-104 <95 N.A. 10/6 10/6 8/10 10/6 10/6
6-11 661 2254 381 1300 26.8 12.3 28.7 295 660 14-104 <95 N.A. 8/10 10/6 8/10 10/6 10/6
8-11 948 3234 551 1882 26.8 12.3 28.7 386 660 14-104 <95 N.A. 6/14 8/10 6/14 8/10 8/10
10-11 1090 3719 556 1896 26.8 12.3 28.7 410 660 14-104 <95 N.A. 4/22 6/14 4/22 8/10 8/10
5-11/120 V 641 2187 425 1451 39.2 12.3 28.7 386 660 14-104 <95 6/14 N.A. N.A. 8/10 10/6 10/6
6-11/120 V 744 2539 601 2051 39.2 12.3 28.7 386 660 14-104 <95
<1000, derating
12.5% per 1000
4/22 N.A. N.A. 8/10 10/6 10/6
Model Minimum free space required
(Inches)
front side rear
Distance between mounting
holes (Inches)
Input overcurrent protection
(AMPS)
Output overcurrent protection (AMPS)
LP-U x y z 120V 208V 240V 120V
(1 X)
120V
(2X)
208V 240V
5-11 4 2 8 7.24 22.76 7.48 35 30 40 20 25 20
5-11 /120V 4 2 8 7.24 22.76 7.48 60 40 20 25 20
6-11 4 2 8 7.24 22.76 7.48 40 35 50 25 30 25
6-11 /120V 4 2 8 7.24 22.76 7.48 70 50 25 30 25
8-11 4 2 8 7.24 22.76 7.48 60 45 70 35 40 35
10-11 4 2 8 7.24 22.76 7.48 70 60 80 40 50 40