GE LP11U Power Supply User Manual


 
LX: OPM_LPU_11U_5K0_10K_1US_V030 41 GE DE LP 11U UPS: Installation / User Manual 3.0 (US)
Digital En
e
rg
y
LP Serie
s
g
UPS Type : 5-11U 6-11U 8-11U 10-11U
AUTOMATIC BYPASS SWITCH
The automatic switch provides transfer of the load to the utility voltage without any interruption of the supply. The transfer is
initiated by a signal from the output converter protection circuit in case of an overload or high temperature.
When the conditions return to normal the load is automatically transferred back to the output converter. The automatic
bypass switch can be disabled by the end-user.
Bypass voltage limits : -15%, +10% of nominal
Transfer transients : typically 2% mean deviation over one half cycle.
Frequency tracking range : ± 2/4/6% of nominal (user selectable)
Slew rate : max. 1Hz/sec or 5Hz/sec (user selectable)
BATTERY
Battery type : Sealed and maintenance free
Nominal voltage (V) / capacity (Ah) : 12/7 12/7 12/12 12/12
Number of batteries : 20 20 20 20
Capacity of standard battery set : 7Ah 7Ah 12Ah 12Ah
Battery recharge time : 1.5 - 3 hours for 80% capacity
Battery service life : up to 6 years (depending on operating conditions)
Battery discharging : self discharge current 0.35 mA
discharge end voltage of the battery depending on the actual load
10.5Vdc < 0.2 CA till 9.0 Vdc > 2 CA
When the UPS is in sleeping mode the inverter will be switched off, battery
charger and rectifier are in operation
Runtime in minutes
VA / Watts
1000 / 800 : 6060 120 120
2000 / 1600 : 4040 60 60
3000 / 2400 : 1818 40 40
5000 / 4000 : 1010 22 22
6000 / 4800 : - 8 17 17
8000 / 6400 : - - 11 11
10000 / 8000 : - - - 8
BATTERY EXTENSION PACKS
Sheet steel cubicle : VSDA1
Dimensions (hxwxd, mm) : 537x313x590
Dimensions (hxwxd, inch) : 21.1x12.3x23.2
Battery : 240Vdc/7Ah or 240Vdc/14Ah
Weight with battery (Kg) : 73 or 123
Weight with battery (Lbs) : 161 or 271
Battery pack A (voltage V / capacity Ah) : 240/7 240/7 240/7 240/7
Total capacity (Ah) : 14 14 19 19
Typical runtime, 100% / 50% load, min. : 25/60 21/50 22/50 16/39
Number of packs required : 1 1 1 1
Battery pack B (voltage V / capacity Ah) : 240/14 240/14 240/14 240/14
Total capacity (Ah) : 21 21 26 26
Typical runtime, 100% / 50% load, min. : 45/90 35/75 33/70 25/57
Number of packs required : 1 1 1 1
For more info see section 7.1
STEP-UP TRANSFORMER CABINET MOUNTED UNDERNEATH VSD2 (FOR LP 5/6-11U ONLY)
Sheet steel cubicle : VSDT2 + VSD2
Dimensions (hxwxd, mm) : 995x313x730
Dimensions (hxwxd, inch) : 39.2x12.3x28.7
Weight (Kg) : 175 Kg
Weight (Lbs) : 386 Lbs