GE LP11U Power Supply User Manual


 
LX: OPM_LPU_11U_5K0_10K_1US_V030 40 GE DE LP 11U UPS: Installation / User Manual 3.0 (US)
Digital En
e
rg
y
LP Serie
s
g
UPS Type : 5-11U 6-11U 8-11U 10-11U
Output power (kVA/kW) : 5/4 6/4.8 8/6.4 10/8
AC input voltage : 120/208/240 Vac (120V only with step-up transformer for LP 5/6-11U)
Input frequency : 60/50 Hz
AC output voltage : 120/208/220/230/240V
Output frequency : 60 or 50 Hz, std. 60 Hz; selectable on front
System efficiency (full load) : 87%
Line input breaker (C-type) : 32A 32A 50A 63A
Bypass input breaker (C-type) : 32A 32A 50A 63A
Battery safety fuse (F4A) : 30A 30A 30A 30A
Battery safety fuse (F4B) : 30A (spare) 30A (spare) 30A 30A
Internal safety fuse (F5A) : - - 30A 30A
Internal safety fuse (F5B) : 30A 30A 30A 30A
Input/output connectors : terminals at rear of unit
INPUT
AC input voltage range (208V-240V)
at 100% load : 162 - 285 V
at 50% load : 146 - 285 V
at 20% load : 133 - 285 V
AC input voltage range (120V, L5/6-11U)
at 100% load : 81 - 141 V
at 50% load : 72 - 141 V
at 20% load : 66 - 141 V
Input frequency range : 40-70 Hz
Input current wave form : sinusoidal
Input power factor : 0.99
Max. input current at 100% load 120V : 43.3A 50.8A n.a. n.a.
208V : 25.0A 30.0A 40.5 50.3
240V : 21.4A 25.1 34.8 42.0
Inrush current : none
Rectified DC voltage out : 380 V
BATTERY CHARGER
Characteristic : U/I-characteristic, constant current charging until boost/float voltage, then
constant voltage charging and boost charge mode for fast recharging of
batteries
DC input voltage range : 350-450 V
DC output voltage at 20 °C : float: 273 V boost: 295 V
Output current limit (Adc) : 2.0 2.0 3.0 3.0
OUTPUT CONVERTER
Output power at pf. = 0.8, VA* : 5000 6000 8000 10000
Semiconductor : IGBT
AC output voltage : 120/208/240V ± 1% static resistive load
120/208/240V ± 2% measured crest load 2.5:1
120/208/240V ± 2% dynamic mean deviation over one half cycle for 100% of
rated load applied or removed
Typical overload : 110% 20 minutes
(temp. dependent) 130% 3.5 minutes
150% 2 minutes
Output frequency : 60 or 50 Hz selectable, ± 0.1%, unless synchronized with the utility
Freq. tracking range : ± 2/4/6% of nominal, user selectable
Output wave form : sine wave
Max. phase difference input-output : max 7°
Harmonic distortion : 2% max. with linear load
Power factor range : Any lagging or leading power factor permitted within the specified rating to
pf. 0.5
Output derating altitude : Till 1000m no derating
Above 1000m 12.5% per 1000m, max. 4000m
Protection : Automatic shut down (or transfer to bypass, if bypass is available) in case of
- low/high DC voltage
- overtemperature
- overload / short circuit
The output is protected against connection to the utility supply
* according to EN 50091-1
10 - Specifications