GE DEH-210 Network Card User Manual


 
PMCS Interface Toolkit Features of Tabular Data Screen Wizards 187
Tab Button Function
Metering Digital Input Labels The user can enter descriptive text
(limited to 22 characters) for each
digital input. These labels are retentive.
Control Trigger Demand Report
Initiates a "current report" download to
a file after prompting the user to
confirm the requested action. Report
status is indicated during the download.
When the report is complete the path to
the new file is displayed.
Block/Unblock Reclosure Blocks or Unblocks the recloser
remotely after confirmation by the user.
Active only if the recloser function is
available in the device. Will not unblock
reclosers blocked locally.
Open/Close Breaker
Opens or closes the breaker attached to
the device after confirmation by the
user. This button is disabled if the
relay’s breaker status input is unwired.
See the relay manual for details.
Control Reset Fault Log Clears the device fault log record after
confirmation by the user.
Reset Event Log Clears the device event log record after
confirmation by the user.
Disable Relay Toggles the relay Enable/Disable
setpoint after confirmation by the user.
Group 1 - 6 Changes the relay’s active setpoint
group to the selected value (1 – 6) after
confirmation by the user.
Table 39. DFP100 Tabular data screen commands.
General notes on controls:
1.
If the communications link between the device and the wizard has failed (as
indicated by the "Communications failed" warning) then all Control tab
command buttons will display the message "Communications Failure – please
wait" in response to command requests.
2.
While a warning or prompt message box is displayed by the wizard, all wizard
controls such as command buttons and tab selectors are disabled.
3.
A 15 second consecutive-command delay is enforced between command
requests. While this delay is in progress, additional command requests will
display the message "Device Busy – please wait".