Honeywell Switches and Sensors Switch User Manual


 
142
www.honeywell.com/sensing
PRESSURE SENSORS
COMMON
V out
+V
0,95
[0.04]
0.43
[0.015]
GT 150
SERIES - 3 PIN
1,
37
[0.05]
7/16-20UNF
GLAND PER MS33656
(3-904 O-RING SEAL
NOT PROVIDED)
STAINLESS STEEL OR
PLATED CRS HOUSING
COMMON
V out
+V
0,95
[0.04]
0,60
[0.02]
1,37
[0.05]
1/4-18NPT
PLATED CRS
HOUSING
GT 150
SERIES - 3 PIN
COMMON
V out
+V
0,95
[0.04]
0.43
[0.015]
GT 150
SERIES - 3 PIN
1,
37
[0.05]
7/16-20UNF
GLAND PER MS33656
(3-904 O-RING SEAL
NOT PROVIDED)
STAINLESS STEEL OR
PLATED CRS HOUSING
COMMON
V out
+V
0,95 [0.04]
0,42 [0.016]
1,37 [0.05]
1/8-27 NPT
STAINLESS STEEL
HOUSING
GT 150
SERIES - 3 PIN
Bonded Element Series
OPTIONS
SS Housing - 1/4 in NPT
MEASUREMENT TYPE PRESSURE RANGE REFERENCE
Gauge 0 psig to 125 psig BE-4R125PG5DS
CRS Housing - 1/4 in NPT
MEASUREMENT TYPE PRESSURE RANGE REFERENCE
Gauge 0 psig to 125 psig BE-4R125PG5DC
SS Housing - 1/8 in NPT
MEASUREMENT TYPE PRESSURE RANGE REFERENCE
Gauge 0 psig to 500 psig BE-4R500PG4DS
SS Housing - 7/16 in - 20 UNF
MEASUREMENT TYPE PRESSURE RANGE REFERENCE
Gauge 0 psig to 5,000 psig BE-4R5000PG6DS
CRS Housing - 7/16 in - 20 UNF
MEASUREMENT TYPE PRESSURE RANGE REFERENCE
Gauge 0 psig to 5,000 psig BE-4R5000PG6DC
COMMON
V out
+V
0,95
[0.04]
0,60
[0.02]
1,37
[0.05]
1/4-18NPT
PLATED CRS
HOUSING
GT 150
SERIES - 3 PIN
The Bonded Element general-purpose industrial pressure transducers were
developed for a variety of pressure applications and industries, providing
excellent media compatibility with all stainless steel wetted parts. It is the ideal
choice for applications where both media compatibility and high cycle life are
essential
Supply voltage: 4.75 Vdc to 5.25 Vdc
Signal conditioning: Amplified
Operating temperature range: -40 °C to 125 °C (-40 °F to 257 °F)
Compensated temperature range: -20 °C to 85 °C (-4 °F to 185 °F)
Output type: 0.5 V to 4.5 V Ratio-metric
Termination type: GT 150 Series - 3 pin