IBM 9308 Personal Computer User Manual


 
Rack PDU specifications
When connected to a properly wired, grounded, and dedicated power source, the
Rack PDU conforms to UL950, CSA 22.0-950, EN-60950, and IEC-950 standards.
The following table contains the product specifications for the Rack PDU:
Height 43 mm (1.7 in.)
Width 192 mm (7.5 in.)
Depth 221 mm (8.7 in.)
Weight 1.6 kg (3.5 lbs)
Operating temperatures 10°C–35°C (50°F–95°F) at 0–914 m (0–3000 ft)
10°C–32 °C (50°F–90°F°) at 914–2133 m (3000–7000 ft)
Operating humidity 8–80% (non-condensing)
Rated voltage 100–120 V ac, 30 A, single-phase
200–240 V ac, 30 A, single-phase
200–240 V ac, 32 A, single-phase
200–240 V ac, 30 A, single-phase
380–415 V ac, 32 A, single-phase
Rated frequency 50–60 Hz
Maximum power rating 4800-6000 VA
Power inlet One fixed line cord
Power outlets Three IEC 320-C19 outlets rated at 16 A (VDE) / 20 A
(UL/CSA)
1
1
2
2
3
3
MAIN
M
AIN
Figure 61. Connecting and routing other power cables to the outlets
154 Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308