Chapter 7 Buffer read/write instructions
7 - 8
7.2.2 RPUT instructions
RPUT FUN(233) RPUT Applicable CPU
K200S
K300S
K1000S
Available devices Flag
Instructions
M P K L F T C S D #D Integer
Steps
Error
(F110)
Zero
(F111)
Carry
(F112)
sl ¡
st
¡
S ¡
D ¡ ¡ ¡ ¡* ¡ ¡ ¡ ¡
n
¡
¡
RPUT
SS ¡ ¡ ¡ ¡* ¡ ¡ ¡ ¡
13
¡
Operand setting
Upper
byte
Type of remote special function
module
sl
Lower
byte
Slot number of Fnet module of
self-station
D
Start address of buffer memory
of A/D module of remote
station
Upper
byte
Slot number of remote special
function module
st
Lower
byte
Station number of Fnet remote
module
n Number of words to be read
S
Start address of device at which source
data is stored (self-station)
SS
Device at which the link status
is stored
* Available only when do not use computer link module or data link module
1) Functions
- Write the data of n words which start at the device specified as ‘S’ to the block which
begin with the address specified as D of buffer memory inside the special function
module of remote station. (station number & slot number is specified as st) through the
Fnet communication module. Then stores the link status into the device specified as ‘SS’
of self-station.
RPUT sl st S D n SS
Input
condition