Liebert 1000kVA Power Supply User Manual


 
Operation
43
The Summary screen (Figure 27) shows Total Number of Discharge Cycles, Accumulated Battery
Time, Accumulated Battery Amp Hours, Accumulated Battery Kilowatt Hours and Battery Tempera-
ture. During a battery discharge event, the screen changes to show information about the present dis-
charge cycle. The screen displays Active Cycle Time in place of Accumulated Battery Time and shows
Active Battery AH and Active Battery kWH instead of accumulated values.
Figure 27 Battery cycle monitoring summary screen
Figure 28 shows a typical detail screen for the 91-240 Seconds Discharge category. This information
can be collected remotely, through the optional communications board and modem, by a remote termi-
nal or a personal computer equipped with a modem and communications program. See 3.2.15 - Com-
munication Interfaces for more information.
Figure 28 Typical data on discharge cycles of 91 to 240 seconds duration during the recording period
NOTE
This information is applicable to systems with separate batteries for each module. If the
modules share a common battery, select one module to do the monitoring and disregard
the other(s).
7
15 min. 32 sec.
71
34
25°C / 77°F
Total No. of Cycles . . . . . . . . . . . . .
Accumulated Battery Time . . . . . . .
Accumulated Battery AH . . . . . . . .
Accumulated Battery KWH . . . . . . .
Battery Temperature . . . . . . . . . . . .
Battery Cycle Monitoring Summary
EXITSELECT :
© 1989-2003
EXIT
Event Date Time Duration Min. Volt Max. Amp Start KW Start Temp
15 4/12/95 10:31 235 477 110 70 68
12 3/25/95 20:21 98 479 97 37 65
9 3/13/95 7:35 139 467 173 69 67
5 2/07/95 17:22 199 478 95 40 70
2 11/24/94 12:33 95 477 83 39 69
Total 91-240 se c. Cycl 5