Liebert 130 kVA Power Supply User Manual


 
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
35
Select MEASUREMENT and press ENTER key.
Select BATTERY and d.c. busbar voltage will be
displayed:
If the voltage indicated is satisfactory (432V d.c. for
380V a.c. system, 446VV d.c. for 400V a.c. system
and 459V d.c. for a 415V a.c. system) press the
Escape key repeatedly until the display returns to
the original window.
6. Manually close the battery circuit breaker. This
is located inside the battery cabinet (if used) or is
otherwise located adjacent to the battery racks.
The Module Mimic indicator (3) Battery unavailable
should extinguish. Several LED’s on the Battery
state of charge bargraph (17) will illuminate
showing the battery state of charge
When the battery circuit breaker has been closed
and the inverter has stabilized the screen will
change to the default window.
Default window:
The message shown below, will be seen on the
default screen whenever the UPS is operating
normally:
The top lines display the UPS operational status
and indicates alarm conditions when they occur;
and line four normally shows the time and date.
The UPS is operating normally with its
Inverter supplying the load.
ECOMODE:
The following message will appear in the default
screen whenever the UPS is operating in
ECOMODE. The load is supplied through Bypass
Mains.
The UPS is operating in ECOMODE with the Bypass
Mains supplying the load.
>MEASUREMENT <
FUNCTION
MAINTENANCE
SETUP
>MEASUREMENT <
FUNCTION
MAINTENANCE
SETUP
OUTPUT
INPUT
>BATTERY <
TEMPERATURE
OUTPUT
INPUT
>BATTERY <
TEMPERATURE
BATTERY
VOLTAGE 446 [V]
CURRENT 001 [A]
CHARGE 000 [%]
BATTERY
VOLTAGE 446 [V]
CURRENT 001 [A]
CHARGE 000 [%]
NORMAL OPERATION
hh.mm.ss dd.mm.yy
NORMAL OPERATION
hh.mm.ss dd.mm.yy
NORMAL OPERATION
(ECOMODE)
hh.mm.ss dd.mm.yy
NORMAL OPERATION
(ECOMODE)
hh.mm.ss dd.mm.yy