Liebert 130 kVA Power Supply User Manual


 
User Manual
Hipulse - Single Phase ‘1+N’ UPS System 130 kVA - 110V
44
5.11 Setting the Battery Test
A software-controlled battery facility can be initiated from the Operator control Panel
on an ‘immediate’ or ‘periodic’ basis. This test turns off the rectifier and runs the
inverter (and load) from the battery from the predetermined period. If the battery
voltage falls below an preset minimum level prior to the termination of the test period
a ‘BATTERY TEST FAILED’ alarm is annunciated and the rectifier is immediately turned
on to prevent the load from transferring to bypass and recharge the battery. These
instructions given below initiates an immediate battery test.
For the following test to be ‘meaningful’ as part of the UPS commissioning procedure,
the batteries should be fully charges prior to the test being carried out. The UPS
rectifier section must be therefore allowed to be operated with the battery connected
for several hours to provide the battery with an adequate initial charge.
CAUTION
Do not continue with this procedure if the battery is not yet charged.
1. From the default window press the ENTER key: the Main Menu window will display.
2. Select FUNCTION and press ENTER key.
3. When the password has been completed press the ENTER key.
4. Select the BATTERY TEST and press ENTER key.
5. Verify that the parameters entered in the battery test set up menu are appropriate. If
not then enter the correct set up parameters (FUNCTION à BATTERY TEST à SET
UP)
6. Press ESC key to return to the battery test menu screen.
7. Using the ‘UP’ menu button, select ‘YES’ (Y), then press enter to initiate an immediate
battery test.
8. Step back to default screen, by continuously pressing the ESC button and verify that
the message: BATTERY UNDER TEST is displayed. The green LED battery bargraph
will indicate the remaining battery time.
Note: If the UPS is allowed to run in this condition the battery bargraph LED’s will progressively
turn off the indicating the remaining autonomy time.
9. The battery will be tested for the selected ‘DURATION’ time after which the UPS will
revert to normal operation.
Note: If the battery fails the test, the rectifier will immediately return to the float mode and the
‘BATTERY: TEST FAILED’ alarm will be displayed on the default screen.