2.0 Scope
This section describes installation requirements, system dimensions, cable connections, and start-up procedures
for the Power-Sure™ 700 Three Phase Power Conditioners.
WARNING: HIGH VOLTAGE, ONLY QUALIFIED ELECTRICIANS SHOULD INSTALL OR
PERFORM MAINTENANCE.
2.1 Installation Notes
The Power-Sure™ 700 requires ventilation. Reference Section 1.3.1 for cabinet placement for each model.
After installation is complete, verify the output voltage is within its rated specifications.
Provide overcurrent protection per article NFPA 70 latest revision article 450-3(b).
Optional output cables must be specified in lengths of 10 feet, cables may have receptacles on the termi-
nating end.
For installation of conduit, reference NEC Article 348 and 350 and any applicable local electrical codes.
Refer to the following installation diagrams for electrical hookup.
2.2 MGE UPS Systems Power-Sure™ 700
An efficient installation depends on careful planning and site preparation. Installation of the equipment must be
handled by skilled technicians and electricians familiar with the special requirements of high-voltage electrical
equipment. The installation must comply with the requirements of the National Electrical Code (ANSI/NFPA 70,
latest issue) and local codes as applicable, and safety standard, UL1012 listed; UL1449 compliant; meets FCC Cat. A.
We strongly recommend contacting MGE for system start-up. Do not allow unqualified personnel to handle, install,
or operate the Power-Sure™ 700.
A good way to insure that the Power-Sure™ 700 is sized properly is to use the following guide lines:
List each piece of equipment, include Model, Voltage, Current and kVA.
Calculate kVA of load plus a safety margin.
When this is not possible, gather the data by reading the specification plate of the equipment you plan on
backing up.
One method is to ask the vendor of the computer equipment to supply you with the information you need.
Be sure to verify the input supply voltage and the output requirements of the Power-Sure™ 700.