Figure 2-2: Power-Sure™ 700 — 25-30kVA Mechanical Cabinet Measurements.
24"
(609.6m)
CLEARANCE FOR
SERVICEABILITY
44"
(1117.6m)
21.5"
(546.1m)
POWER ON
ALERT
INPUT CIRCUIT BREAKER
BYPASS SWITCH (OPTIONAL)
INPUT TERMINALS
ALLEN BRADLEY 31492 -CE2
#12-I/O WIRE
INPUT GROUND TERMINAL
ILSCD #TA-2
#2-#14 WIRE
HOLE PROVIDED FOR
1 INPUT CONDUIT
OUTPUT DISTRIBUTION
(OPTIONAL)
HOLE PROVIDED
1 OUTPUT CONDUIT
OUTPUT TERMINALS
ILSCOTA2/0 WIRE RANGE: #14 AWG-2/0
PK9 WIRE RANGE: 14GA. -#4AWG
FRONT VIEW RIGHT SIDE VIEW REAR VIEW
29"
(736.6m)
TOP VIEW
12"
(304.8m)
FOR INSTALLATION
PURPOSES ONLY
COOLING
FANS
12"
(304.8m)
FOR INSTALLATION
PURPOSES ONLY
ENVIRONMENTAL
CLEARNESS
TO REMOVE TOP: REMOVE RETAINING SCREW IN REAR OF TOP,
LIFT REAR AND SLIDE FORWARD
TO REMOVE SIDE: REMOVE RETAINING SCREW IN TOP OF PANEL,
LIFT PANEL STRAIGHT UP
Installation and Operation
2 — 3
Installation and User Manual
86-108814-00 B01