MGE UPS Systems EPS 7000 Power Supply User Manual


 
Users Manual
Operation
page 2 —1
2.0 Scope
This section describes procedures for normal operation of EPS 7000 Single Module systems. Including interactive
front panel display, settings for language configuration, alarms message displays, voltage, current, battery measure-
ments, with before and after start-up checks, emergency shutdown using EPO disconnects, and normal conditions
for using forced transfers.
2.1 Status Screen Display
The alphanumeric interactive status screen display, (located in the top pane of the hidden panel, see Figure 1-8), is
the automatic default display for status setting configurations.
Figure 2-1: Default Status Screen Alphanumerical Display Configuration.
During normal operation, when there are no alarm conditions present and the load is supplied by the UPS inverter
output, the display will present the general status message:
LOAD IS PROTECTED
UPS IS ON LINE
When there are alarm conditions, the display will present a general alarm message, and the user can use the
“alarm” pushbutton (!) to determine the exact cause of the alarm condition, see section 2.9, Alarms.
The following sections present detailed operating instructions for the alphanumeric display.
Operation
General status screen.
This is the default display. It automatically reappears
if the control panel has not been used for ten minutes.
Alarm display
Voltage measurements
Current measurements
Frequency and power measurements
Battery measurements
Reserved for future use (on/off controls)
Language and screen contrast settings
V
+
!
A
W.Hz
°
to
set
to
confirm
to
confirm
*