Mitsubishi Electronics Q02HCPU Electronic Accessory User Manual


 
11 - 32 11 - 32
MELSEC-Q
11 TROUBLESHOOTING
Error Code
(SD0)
1
Error Contents and Cause Corrective Action
Corres-
ponding
CPU
The refresh setting of the intelligent function module exceeded the
file register capacity.
Change the file register file for the one which allows refresh in the
whole range.
QCPU
function
Ver. B
or later
3301
The intelligent function module's refresh parameter setting is
outside the available range.
Check the parameter setting.
QCPU
Rem
3302 The intelligent function module's refresh parameter are abnormal. Check the parameter setting. QCPU
3303
In a multiple CPU system, automatic refresh setting or similar
parameter setting was made to the intelligent function module under
control of another station.
(1) Delete the automatic refresh setting or similar parameter setting
of the intelligent function module under control of another
station.
(2) Change the setting to the automatic refresh setting or similar
parameter setting of the intelligent function module under control
of the host station.
3400
The first I/O number of the target module in the remote password
file is set to other than 0
H
to 0FF0
H
.
Change the first I/O number of the target module to within the 0
H
to
0FF0
H
range.
Position specified as the first I/O number of the remote password
file is incorrect due to one of the following reasons:
• Module is not loaded.
• Other than a Q-compatible intelligent function module (I/O, A, QnA
module)
• Intelligent function module other than QJ71C24(-R2) or Q series
Ethernet interface module
• QJ71C24(-R2) or Q series Ethernet interface module of function
version A
Load the QJ71C24(-R2) or Q series Ethernet interface module of
function version B in the position specified as the first I/O number of
the remote password file.
3401
QJ71C24(-R2) or Q series Ethernet interface module of function
version B under control of another station is specified in a multiple
CPU system.
(1) Change the setting to the QJ71C24(-R2) or Q series Ethernet
interface module of function version B under control of the host
station.
(2) Delete the remote password setting.
QCPU
function
Ver. B
or later
4000
The program contains an instruction code that cannot be decoded.
An unusable instruction is included in the program.
4001
The program contains a dedicated instruction for SFC program
although it is not an SFC program.
4002
The extension instruction designated by the program has an
incorrect instruction name.
4003
The extension instruction designated by the program has an
incorrect number of devices.
Read the common error information at a peripheral device, check
error step corresponding to its numerical value (program error
location), and correct the problem.
Rem
4004
The extension instruction designated by the program a device which
cannot be used.
Read the common error information at a peripheral device, check
error step corresponding to its numerical value (program error
location), and correct the problem.
4010 There is no END (FEND) instruction in the program.
4020
The total number of internal file pointers used by the program
exceeds the number of internal file pointers set in the parameters.
4021 The common pointer numbers used by individual files overlap.
4030 The allocation pointer numbers used by individual files are overlap.
Read the common error information at a peripheral device, check
error step corresponding to its numerical value (program error
location), and correct the problem.
4100 The instruction cannot process the contained data.
4101
The designated device number for data processed by the instruction
exceeds the usable range.
Alternatively, the stored data or constants for the devices
designated by the instruction exceeds the usable range.
Read the common error information at a peripheral device, check
error step corresponding to its numerical value (program error
location), and correct the problem.
In a multiple CPU system, the link direct device (J \G ) was
specified for the network module under control of another station.
(1) Delete from the program the link direct device which specifies
the network module under control of another station.
(2) Using the link direct device, specify the network module under
control of the host station.
QCPU
function
Ver. B
or later
4102
The network number and station number designated with a
dedicated network instruction are not correct.
The link direct device (J
\W
) is not set correctly.
• The module No./network No./character string count specified by
the extension instruction is outside the setting range.
• The character string (" ") specified by the extension instruction is
unusable.
Rem
4103
The configuration of the PID dedicated instruction is incorrect.
Read the common error information at a peripheral device, check
error step corresponding to its numerical value (program error
location), and correct the problem.
33 or more multiple CPU dedicated instructions were executed from
one CPU module.
Using the multiple CPU dedicated instruction completion bit, provide
interlocks to prevent one CPU module from executing 32 or more
multiple CPU dedicated instructions.
QCPU
function
Ver. B
or later
4107
Numbers of execution to the CC-Link instruction are beyond 64.
Set the numbers of execution to the CC-Link instruction to 64 or
less.
4108
The CC-Link parameter is not set when the CC-Link instruction is
executed.
Execute the CC-Link instruction after setting the CC-Link
parameter.
QnA
4109
With high speed interrupt setting execute
PR/PRC,UDCNT1/2,PWM,SPD,PLOADP,PUNLOADP,PAWPP
instruction.
Read the common error information at a peripheral device, check
error step corresponding to its numerical value (program error
location), and correct the problem.
QCPU
serial
No.
04012
or later
No NEXT instruction was executed following the execution of a
FOR instruction.
4200
Alternatively, there are fewer NEXT instructions than FOR
instructions.
Read the common error information at a peripheral device, check
error step corresponding to its numerical value (program error
location), and correct the problem.
A NEXT instruction was executed although no FOR instruction has
been executed.
4201
Alternatively, there are more NEXT instructions than FOR
instructions.
Read the common error information at a peripheral device, check
error step corresponding to its numerical value (program error
location), and correct the problem.
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.