Omega RD100B Microcassette Recorder User Manual


 
7-2
Select On to set relays I01, I02, and I03
to reflash alarm operation.
Select On to set relay I01 to diagnosis
output.
Select the range of relays that are to
operate using AND logic.
Select the relay’s energized or
de-energized operation.
Select the relay’s hold or non-hold
operation.
Select the relay’s hold or non-hold
operation.
Set the interval of the high limit on
rate-of-change alarm.
Set the interval of the low limit on
rate-of-change alarm.
Set the hysteresis of the measurement
channels.
Set the hysteresis of the computation
channels.
(models with /M1)
The new setting takes effect.
ESC/?
Basic=Alarm
Diagnosis=Off
Reflash=Off
AND=None
Act=Energize
Behavior=Nonhold
Indicator=Nonhold
Increase=01
Decrease=01
Hysteresis=0.5%
M_Hysteresis=0.0%
Alarm
Setting complete
Applying the Changes and Returning to Operation Mode
Press the
key or SHIFT + key to select End and then press the key. Press
the key to select Store and then press the key. The changes are applied, and
the screen returns to Operation mode. If you select Abort and press the key, the
changes are discarded, and the screen returns to Operation mode. Press the ESC key
to return to the Basic= screen.
Explanation
Diagnosis
When set to On, alarm output relay I01 becomes a dedicated diagnosis output relay, and
the operation is fixed to OR, de-energized, and non-hold. Diagnosis output is a function
which outputs a relay signal when an error is detected in the recording section, burnout
detection function, or the A/D converter.
7.1 Changing the Auxiliary Alarm Function