Omron NT631 Printer User Manual


 
263
Using an RS-232C/RS-422A Adapter Appendix C
Pin Arrangement
The Adapter has a terminal block for an RS-422A/485 interface connection and a connector for an RS-232C
interface connection.
The pin arrangements for the RS-422A/485 terminal block and the RS-232C connector are as follows.
RS-422A/485 Terminal Block
* The CSB and CSA signals are for specialized applications.
RS-232C Connector
* The hood is connected to the functional ground terminal of the RS-422A terminal block.
Terminal
block pin
No.
Signal name Abbreviation Signal direction
(Adapter RS-422 device)
8 Request to send ()CSA
7 Request to send (+) CSB
6 Receive data ()RDA
5 Receive data (+) RDB
4 Send data ()SDA
3 Send data (+) SDB
2 Signal ground SG (GND)
1 Functional ground
Connector
pin No.
Signal name Abbreviation Signal direction
(Adapter RS-232C device)
1 Not used
2 Send data SD
3 Receive data RD
4 Request to send
(shorted to CS internally)
RS
5 Clear to send
(shorted to RS internally)
CS
6 +5 V (150 mA) input for Adapter +5 V
7 Data set ready
(shorted to ER internally)
DR
8 Data terminal ready
(shorted to DR internally)
ER
9 Signal ground SG
7
5
3
1
8
6
4
2
6
7
8
9
1
2
3
4
5