Perle Systems RPS830 Switch User Manual


 
6-6
RPS Series: Remote Power Switches - User's Guide
6.2.3. Applying Commands to Several Plugs - Text Interface
As described below, switching and reboot commands can be applied to only
one Switched AC Outlet, or to an assortment of outlets.
Notes:
When switching or reboot operations are initiated, Boot/
Sequence Delay times will be applied as described in
Section 5.3.3.2.
Switching and reboot commands will only be applied to the
outlets that are allowed by the password that was used to access
command mode.
1. Several Plugs: To apply a switching or reboot command to several
plugs, enter the numbers or names for the plugs, separated by a "plus
sign" (+). For example to switch plugs 1, 4, and 5 Off, enter the
following:
/OFF 1+4+5 [Enter]
2. Series of Plugs: To apply a command to a series of RPS Plugs, enter
the number for the plugs that mark the beginning and end of the series,
separated by a colon. For example, to switch plugs 1 through 3 On,
enter the following:
/ON 1:3 [Enter]
4. All Plugs: To apply a command to all plugs, enter an asterisk in place
of the name or number. For example, to Boot all plugs, enter the
following:
/BO * [Enter]