Perle Systems RPS830 Switch User Manual


 
Apx-2
RPS Series: Remote Power Switches - User's Guide
B. Specifications
Power Input / Output:
Model RPS820 (208 to 240 VAC)
AC Input: Two Separate Circuits; 10 Amps Maximum per Circuit
Voltage: 208 - 240 VAC 50/60 Hz
Connectors: Two (2) IEC-320-C14 Inlets
AC Outputs:
Connectors: Eight (8) IEC-320-C13 Outlets, Split into Two 10 Amp Circuits
Load: 10 Amps per Circuit; providing a Maximum Total of 20 Amps
Model RPS830 (100 to 120 VAC)
AC Input: Two Separate Circuits; 15 Amps Maximum per Circuit
Voltage: 100 - 120 VAC 50/60 Hz
Connectors: Two (2) IEC-320-C14 Inlets, Line Cords Supplied
AC Outputs:
Connectors: Eight (8) NEMA 5-15 Outlets, Split into Two 15 Amp Circuits
Load: 15 Amps per Circuit; providing a Maximum Total of 30 Amps
Model RPS1620 (208 to 240 VAC)
AC Input: Two Separate Circuits; 10 Amps Maximum per Circuit
Voltage: 208 - 240 VAC 50/60 Hz
Connectors: Two (2) IEC-320-C14 Inlets
AC Outputs:
Connectors: Sixteen (16) IEC-320-C13 Outlets, Split into
Two 10 Amp Circuits
Load: 10 Amps per Circuit; providing a Maximum Total of 20 Amps
Model RPS1630 (100 to 120 VAC)
AC Input: Two Separate Circuits; 15 Amps Maximum per Circuit
Voltage: 105 - 120 VAC 60 Hz
Connectors: Two (2) IEC-320-C14 Inlets, Line Cords Supplied
AC Outputs:
Connectors: Sixteen (16) NEMA 5-15 Outlets, Split into
Two 15 Amp Circuits
Load: 15 Amps per Circuit; providing a Maximum Total of 30 Amps
Console / Modem Port Interface:
Connector: DB9M, RS232C, DTE
Coding: Serial ASCII, 8 Bits, No Parity