Powerware 2500 Power Supply User Manual


 
OPERATION
EATON Powerware
®
9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
36
Turning the UPS Off
NOTE Pressing the Off button while the UPS is in Battery mode causes the UPS to shut
down immediately.
To turn off the UPS:
1. Prepare your equipment for shutdown.
2. Press and hold the Off
button for approximately three seconds.
The UPS transfers to Standby mode (if utility power is available) and
removes power from your equipment.
3. Unplug or remove utility power from the UPS; the UPS shuts down
in five seconds. All front panel indicators flash briefly prior to
shutdown.
If you do not unplug or remove utility power from the UPS, it
remains in Standby mode.
Initiating the Self-Test
NOTE The batteries must be fully charged and the UPS must not be in Battery mode to
perform the self-test.
NOTE AC input power must be applied to the UPS for 24 hours before performing the
self-test.
Press and hold the button for three seconds to initiate the self-test.
During the five-second test, the bar graph indicators cycle through twice.
If the alarm beeps or a UPS alarm indicator stays on, see Table 11 on
page 64.