Powerware 2500 Power Supply User Manual


 
CONFIGURATION
EATON Powerware
®
9125 Two-in-One UPS (2500/3000 VA) User’s Guide S 164201374 Rev D
www.powerware.com
43
Table 2. Configuration Mode LEDs and Options
Configuration Mode
LEDs
Option LED Status Explanation
120, 208, or 230V
Nominal Input
Voltage
On (default) Nominal input voltage is one of the following:
S 120V for U models
S 208V for EU/EUH and G/GH models
S 230V for E/EH models
All other nominal input voltages are disabled.
Flashing Disabled; one of the other input voltage options is
selected.
110, 220, or 230V
Nominal Input
Voltage
On Selecting this option changes the nominal input voltage
to one of the following:
S 110V for U models
S 220V for E/EH models
S 230V for EU/EUH and G/GH models
Flashing Disabled; one of the other input voltage options is
selected.
127 or 240V Nominal
Input Voltage
On Selecting this option changes the nominal input voltage
to one of the following:
S 127V for U models
S 240V for EU/EUH, E/EH, and G/GH models
Flashing Disabled; one of the other input voltage options is
selected.
Site Wiring Fault
Alarm
On (default) Alarm sounds when the polarity of the outlet is reversed
or the ground connection is missing; have a qualified
electrician repair the outlet wiring.
Flashing* Alarm DOES NOT sound when the polarity of the outlet is
reversed or the ground connection is missing.
* For 208V or 230V models, flashing is the default; contact
your service representative to activate this alarm.
AC Input Failure
A
l
a
r
m
On (default) Alarm sounds when there is an AC input failure.
Alarm
Flashing Alarm DOES NOT sound when there is an AC input
failure.